LAPSE:2023.3802
Published Article

LAPSE:2023.3802
Estimating the Error of Fault Location on Overhead Power Lines by Emergency State Parameters Using an Analytical Technique
February 22, 2023
Abstract
Fault location on overhead power lines achieved with the highest possible accuracy can reduce the time to locate faults. This contributes to ensuring the stability of power systems, as well as the reliability of power supply to consumers. There are a number of known mathematical techniques based on different physical principles that are used in fault location on overhead power lines and whose errors vary. Fault location on overhead power lines uses techniques based on the estimation of emergency state parameters, which are referred to as distance-to-fault techniques and are widely used. They are employed in digital protection relay terminals and power-line fault locators. Factors that have a significant impact on the error of fault location on overhead power lines by emergency state parameters are design, manufacturing, and operation. The aim of this article is to analyze the existing techniques and to present a new analytical technique for estimating errors of fault location on overhead power lines by using emergency state parameters. The technique developed by the authors makes it possible to properly take into account a set of random factors, including various measurement errors of currents and voltages in the emergency state, which have a significant impact on the fault location on overhead power lines error. The technique allows one to determine more accurately the fault location and the size of the inspection area, which is necessary to reduce the time it takes to carry out emergency recovery operations. The proposed technique can be applied in fault locators and digital protection relay terminals that use both single-end, double- and multi-end sensing of currents and voltages in the emergency state.
Fault location on overhead power lines achieved with the highest possible accuracy can reduce the time to locate faults. This contributes to ensuring the stability of power systems, as well as the reliability of power supply to consumers. There are a number of known mathematical techniques based on different physical principles that are used in fault location on overhead power lines and whose errors vary. Fault location on overhead power lines uses techniques based on the estimation of emergency state parameters, which are referred to as distance-to-fault techniques and are widely used. They are employed in digital protection relay terminals and power-line fault locators. Factors that have a significant impact on the error of fault location on overhead power lines by emergency state parameters are design, manufacturing, and operation. The aim of this article is to analyze the existing techniques and to present a new analytical technique for estimating errors of fault location on overhead power lines by using emergency state parameters. The technique developed by the authors makes it possible to properly take into account a set of random factors, including various measurement errors of currents and voltages in the emergency state, which have a significant impact on the fault location on overhead power lines error. The technique allows one to determine more accurately the fault location and the size of the inspection area, which is necessary to reduce the time it takes to carry out emergency recovery operations. The proposed technique can be applied in fault locators and digital protection relay terminals that use both single-end, double- and multi-end sensing of currents and voltages in the emergency state.
Record ID
Keywords
analytical technique, emergency state parameters, error, fault location, overhead power line, Simulation
Subject
Suggested Citation
Kulikov A, Ilyushin P, Suslov K, Filippov S. Estimating the Error of Fault Location on Overhead Power Lines by Emergency State Parameters Using an Analytical Technique. (2023). LAPSE:2023.3802
Author Affiliations
Kulikov A: Department of Electroenergetics, Power Supply and Power Electronics, Nizhny Novgorod State Technical University n.a. R.E. Alekseev, 603950 Nizhny Novgorod, Russia
Ilyushin P: Department of Research on the Relationship between Energy and the Economy, Energy Research Institute of the Russian Academy of Sciences, 117186 Moscow, Russia [ORCID]
Suslov K: Department of Hydropower and Renewable Energy, National Research University “Moscow Power Engineering Institute”, 111250 Moscow, Russia; Department of Power Supply and Electrical Engineering, Irkutsk National Research Technical University, 664074 Irku [ORCID]
Filippov S: Department of Research on the Relationship between Energy and the Economy, Energy Research Institute of the Russian Academy of Sciences, 117186 Moscow, Russia
Ilyushin P: Department of Research on the Relationship between Energy and the Economy, Energy Research Institute of the Russian Academy of Sciences, 117186 Moscow, Russia [ORCID]
Suslov K: Department of Hydropower and Renewable Energy, National Research University “Moscow Power Engineering Institute”, 111250 Moscow, Russia; Department of Power Supply and Electrical Engineering, Irkutsk National Research Technical University, 664074 Irku [ORCID]
Filippov S: Department of Research on the Relationship between Energy and the Economy, Energy Research Institute of the Russian Academy of Sciences, 117186 Moscow, Russia
Journal Name
Energies
Volume
16
Issue
3
First Page
1552
Year
2023
Publication Date
2023-02-03
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en16031552, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.3802
This Record
External Link

https://doi.org/10.3390/en16031552
Publisher Version
Download
Meta
Record Statistics
Record Views
198
Version History
[v1] (Original Submission)
Feb 22, 2023
Verified by curator on
Feb 22, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.3802
Record Owner
Auto Uploader for LAPSE
Links to Related Works