3D Mapping of the Sprinkler Activation Time
March 23, 2023
Sprinkler activation is one of the key events defining the course of a compartment fire. The time when activation occurs is commonly used in the determination of the design fire scenario, which is the cornerstone of the design of building fire safety features. A well-known model of sprinkler activation (response time index (RTI) model) was introduced into the numerical scheme of the ANSYS Fluent computational fluid dynamics (CFD) package. The novel way in which the model is used is the calculation of the time for sprinkler activation within each discrete cell of the domain. The proposed novel approach was used in a case-study to assess the effects of comfort mode natural ventilation on a sprinkler’s activation pattern. It was found that hinged vents in the comfort mode had a significant effect on sprinkler activation, both in terms of delaying it as well as limiting the total number of cells in which the sprinkler would have activated. In some scenarios with a hinged vent, no activation was observed in the central point of the vent, possibly indicating problems with the autonomous triggering of the fire mode of such a device. It was also found that the RTI and C (related to the conductive transport of sprinkler fitting) parameter values had a moderate influence on sprinkler activation time—only for high-temperature sprinklers (≥ 141 °C). This study shows the applicability of the 3D activation time mapping for research focused on the fire safety of sprinkler-protected compartments and for the performance-based approach to sprinkler system design. Even though the RTI model is the industry standard for the determination of sprinkler response, the model implementation in ANSYS Fluent was not validated. This means that sources of uncertainty, mainly connected with the determination of flow velocity and temperature are not known, and the model should be used with caution. An in-depth validation is planned for subsequent studies.
Keywords
Computational Fluid Dynamics, detection, fire, performance-based design, smoke management, suppression
Suggested Citation
Węgrzyński W, Krajewski G, Tofiło P, Jahn W, Król A, Król M. 3D Mapping of the Sprinkler Activation Time. (2023). LAPSE:2023.22220
Author Affiliations
Węgrzyński W: Fire Research Department, Instytut Techniki Budowlanej, 1 Filtrowa St., 00-611 Warsaw, Poland [ORCID]
Krajewski G: Fire Research Department, Instytut Techniki Budowlanej, 1 Filtrowa St., 00-611 Warsaw, Poland
Tofiło P: The Main School of Fire Service (SGSP), ul. Słowackiego 52/54, 01-629 Warsaw, Poland
Jahn W: Department of Mechanical and Metallurgical Engineering, School of Engineering, Pontificia Universidad Católica de Chile, Vicuña Mackenna 4860, Santiago de Chile 7820436, Chile [ORCID]
Król A: Faculty of Transport, Silesian University of Technology, Krasińskiego 8, 40-019 Katowice, Poland [ORCID]
Król M: Faculty of Energy and Environmental Engineering, Silesian University of Technology, Konarskiego 18, 44-100 Gliwice, Poland [ORCID]
Journal Name
Energies
Volume
13
Issue
6
Article Number
E1450
Year
2020
Publication Date
2020-03-20
Published Version
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en13061450, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.22220
This Record
External Link

doi:10.3390/en13061450
Publisher Version
Download
Files
[Download 1v1.pdf] (7.5 MB)
Mar 23, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
70
Version History
[v1] (Original Submission)
Mar 23, 2023
 
Verified by curator on
Mar 23, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.22220
 
Original Submitter
Auto Uploader for LAPSE
Links to Related Works
Directly Related to This Work
Publisher Version