Cooling Performance Assessment of a Slinky Closed Loop Lake Water Heat Pump System under the Climate Conditions of Pakistan
Muhammad Kashif Shahzad, Mirza Abdullah Rehan, Muzaffar Ali, Azeem Mustafa, Zafar Abbas, Muhammad Mujtaba, Muhammad Imran Akram, Muhammad Rabeet Yousaf
November 24, 2019
This paper presents an experimental evaluation of a closed loop lake water heat pump (LWHPs) system based on the slinky coiled configuration. Initially, a mathematical model is developed in the Engineering Equation Solver (EES) for the heat pump system and the submerged coils in a lake. System performance is determined for the submerged slinky copper coils under the various operating conditions. Afterwards, parametric analysis is performed considering different influencing parameters, such as the lake water temperature, ambient temperature, and mass flow rate of the circulating fluid at constant lake depth of 4 ft. The experimental setup is developed for 3.51 kW cooling capacity after cooling load calculation for a small room. In the current study, slinky copper coils are used to exchange heat with lake water. The experimental setup is installed in Taxila, Pakistan, and the system’s performance is analyzed during selected days. After experimentation based on hourly and daily operation characteristics, it is observed that the lake water temperature has significant influence on the heat transfer rate between slinky coil and lake water. While the lake water temperature in summer decreases and increases in winter with the depth. The resulted daily average coefficient of performance (COP) of the system is within the range of 3.24−3.46 during the selected days of cooling season. Based on these results, it can be concluded that the LWHP systems can be considered a viable solution for Pakistan having a well-established canal system.
Keywords
coefficient of performance, EES modeling, lake water heat pump, Pakistan, Slinky coils
Suggested Citation
Shahzad MK, Rehan MA, Ali M, Mustafa A, Abbas Z, Mujtaba M, Akram MI, Yousaf MR. Cooling Performance Assessment of a Slinky Closed Loop Lake Water Heat Pump System under the Climate Conditions of Pakistan. (2019). LAPSE:2019.1142
Author Affiliations
Shahzad MK: Energy Engineering Department, University of Engineering and Technology, Taxila 47080, Pakistan
Rehan MA: Department of Mechanical Engineering, Pakistan Institute of Engineering and Technology, Multan 60000, Pakistan
Ali M: Energy Engineering Department, University of Engineering and Technology, Taxila 47080, Pakistan [ORCID]
Mustafa A: Department of Mechanical Engineering, Pakistan Institute of Engineering and Technology, Multan 60000, Pakistan
Abbas Z: Department of Mechanical Engineering, Pakistan Institute of Engineering and Technology, Multan 60000, Pakistan
Mujtaba M: Department of Mechanical Engineering, Pakistan Institute of Engineering and Technology, Multan 60000, Pakistan
Akram MI: Department of Mechanical Engineering, Pakistan Institute of Engineering and Technology, Multan 60000, Pakistan
Yousaf MR: Department of Mechanical Engineering, Pakistan Institute of Engineering and Technology, Multan 60000, Pakistan
[Login] to see author email addresses.
Journal Name
Processes
Volume
7
Issue
9
Article Number
E553
Year
2019
Publication Date
2019-08-22
Published Version
ISSN
2227-9717
Version Comments
Original Submission
Other Meta
PII: pr7090553, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2019.1142
This Record
External Link

doi:10.3390/pr7090553
Publisher Version
Download
Files
[Download 1v1.pdf] (5.2 MB)
Nov 24, 2019
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
413
Version History
[v1] (Original Submission)
Nov 24, 2019
 
Verified by curator on
Nov 24, 2019
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2019.1142
 
Original Submitter
Calvin Tsay
Links to Related Works
Directly Related to This Work
Publisher Version