A Hybrid Approach for Low-Voltage AC Series Arc Fault Detection
Yu-Jen Liu, Cheng-I Chen, Wei-Chung Fu, Yih-Der Lee, Chin-Chan Cheng, Yen-Fu Chen
February 22, 2023
Abstract
In a low-voltage electric distribution network, arc fault presents a high energy density electricity-discharging phenomenon between conductors, which is often caused by aging of electric facilities, loose contacts and terminals, or insulation failure due to internal and external destructions. A large amount of heat may be created during this discharging, which will further cause the risk of fire hazards to mitigate in the residential environment. Currently, many utility grid operators and electricity users are still devoted to seeking effective detection technology for arc fault protection. This paper proposes a hybrid approach that combines discrete wavelet transform (DWT), empirical mode decomposition (EMD), and dynamic time warping (DTW) methods for low-voltage AC series arc fault detection. In DWT, it uses time−frequency domain characteristics of the arc current signal to extract the occurrence of arc fault. In EMD, it decomposes the complex arc fault current signal into a finite intrinsic mode (IMF) signal; then, instantaneous amplitude of IMF signal is obtained by Hilbert−Huang transform (HHT) as a feature for arc fault identification. Firstly, the results of arc fault detections depend on the results from DWT and EMD. When both two methods detect different results, DTW method will be activated, using the similarity measurements between normal and arc fault current waveforms as an assistant measure to determine the occurrence of arc fault. The performance of the proposed approach is tested and validated using various electric appliances, and the results show that the proposed approach can effectively detect low-voltage AC series arc fault.
Keywords
arc fault detection, discrete wavelet transform, dynamic time warping, empirical mode decomposition, series arc fault
Suggested Citation
Liu YJ, Chen CI, Fu WC, Lee YD, Cheng CC, Chen YF. A Hybrid Approach for Low-Voltage AC Series Arc Fault Detection. (2023). LAPSE:2023.3523
Author Affiliations
Liu YJ: Department of Electrical Engineering, National Chung Cheng University, Chia-Yi 621301, Taiwan
Chen CI: Department of Electrical Engineering, National Central University, Taoyuan 320317, Taiwan [ORCID]
Fu WC: Department of Electrical Engineering, National Chung Cheng University, Chia-Yi 621301, Taiwan
Lee YD: Nuclear Instrumentation Division, Institute of Nuclear Energy Research, Taoyuan 325207, Taiwan
Cheng CC: Nuclear Instrumentation Division, Institute of Nuclear Energy Research, Taoyuan 325207, Taiwan
Chen YF: Nuclear Instrumentation Division, Institute of Nuclear Energy Research, Taoyuan 325207, Taiwan
Journal Name
Energies
Volume
16
Issue
3
First Page
1256
Year
2023
Publication Date
2023-01-24
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en16031256, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.3523
This Record
External Link

https://doi.org/10.3390/en16031256
Publisher Version
Download
Files
Feb 22, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
340
Version History
[v1] (Original Submission)
Feb 22, 2023
 
Verified by curator on
Feb 22, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
http://psecommunity.org/LAPSE:2023.3523
 
Record Owner
Auto Uploader for LAPSE
Links to Related Works
Directly Related to This Work
Publisher Version
(0.08 seconds)

[0.08 s]