HVAC Operation Schemes and Commissioning Process Resolving Stack Effect Problem and Adjusting According to Changes in the Environment: A Case Study in High-Rise Building in South Korea
April 19, 2023
Abstract
Various problems often arise in high-rise buildings during the winter months due to the stack effect. In this study, the high-rise building of interest, located in South Korea, was experiencing constant loud noises in the winter due to the stack effect. Thus, we created a noise level reduction plan by creating a method for pressurizing the high-rise zones of the building according to outdoor conditions. To discover the appropriate pressurization operating modes, we applied a two-year commissioning process to the 50-story building of interest. The 1st- and 47th-floor elevator halls were identified to have the highest noise levels of all other floors. Prior to applying the reduction plan, the maximum noise level on the first floor with the HVAC system turned off was 85 dB(A) and with the HVAC system turned on it was 70 dB(A). Both values exceeded the criteria of 57 dB(A) for a lobby space of a commercial building. In the case of the 47th floor, the maximum noise level with the HVAC system turned off was 58.7 dB(A) and with the HVAC system turned off was 56.0 dB(A), despite the latter having increased airtightness performance and applying preliminary pressurization (i.e., HVAC operation mode 2). These values exceeded the criteria of 48 dB(A) for an elevator hall in a commercial building. Following this initial data, we determined to pressurize the high/mid-rise zones of the building according to the outdoor air temperature and wind velocity conditions, which we categorized into four types (i.e., HVAC operation mode 4). To this effect, the first-floor elevator hall’s maximum noise level was 56.6 dB(A), meeting the criteria, and the 47th-floor elevator hall’s maximum noise level was 49.5 dB(A), still exceeding the criteria but by an insignificant amount. Although the HVAC pressurization operation we utilized resulted in favorable results for the target building A, it may not be as effective in other new high-rise buildings, creating changes to the indoor air environment or to the energy costs in maintaining a building. However, for the purposes of resolving the stack effect, we believe that the commissioning process we took to optimize the HVAC operation that is presented here can be applied to other new and existing high-rise commercial buildings.
Various problems often arise in high-rise buildings during the winter months due to the stack effect. In this study, the high-rise building of interest, located in South Korea, was experiencing constant loud noises in the winter due to the stack effect. Thus, we created a noise level reduction plan by creating a method for pressurizing the high-rise zones of the building according to outdoor conditions. To discover the appropriate pressurization operating modes, we applied a two-year commissioning process to the 50-story building of interest. The 1st- and 47th-floor elevator halls were identified to have the highest noise levels of all other floors. Prior to applying the reduction plan, the maximum noise level on the first floor with the HVAC system turned off was 85 dB(A) and with the HVAC system turned on it was 70 dB(A). Both values exceeded the criteria of 57 dB(A) for a lobby space of a commercial building. In the case of the 47th floor, the maximum noise level with the HVAC system turned off was 58.7 dB(A) and with the HVAC system turned off was 56.0 dB(A), despite the latter having increased airtightness performance and applying preliminary pressurization (i.e., HVAC operation mode 2). These values exceeded the criteria of 48 dB(A) for an elevator hall in a commercial building. Following this initial data, we determined to pressurize the high/mid-rise zones of the building according to the outdoor air temperature and wind velocity conditions, which we categorized into four types (i.e., HVAC operation mode 4). To this effect, the first-floor elevator hall’s maximum noise level was 56.6 dB(A), meeting the criteria, and the 47th-floor elevator hall’s maximum noise level was 49.5 dB(A), still exceeding the criteria but by an insignificant amount. Although the HVAC pressurization operation we utilized resulted in favorable results for the target building A, it may not be as effective in other new high-rise buildings, creating changes to the indoor air environment or to the energy costs in maintaining a building. However, for the purposes of resolving the stack effect, we believe that the commissioning process we took to optimize the HVAC operation that is presented here can be applied to other new and existing high-rise commercial buildings.
Record ID
Keywords
commissioning process, high-rise buildings, HVAC pressurization, outdoor conditions, stack effect
Subject
Suggested Citation
Yu J, Kim A, Bae S, Cho D, Kim KH. HVAC Operation Schemes and Commissioning Process Resolving Stack Effect Problem and Adjusting According to Changes in the Environment: A Case Study in High-Rise Building in South Korea. (2023). LAPSE:2023.31767
Author Affiliations
Yu J: Indoor Air Quality Research Center, Korea Institute of Civil Engineering and Building Technology, Goyang-Si 10223, Korea [ORCID]
Kim A: Department of Biology, Amherst College, 220 South Pleasant Street, Amherst, MA 01002, USA [ORCID]
Bae S: Indoor Air Quality Research Center, Korea Institute of Civil Engineering and Building Technology, Goyang-Si 10223, Korea
Cho D: Department of Living and Built Environment Research, Korea Institute of Civil Engineering and Building Technology, Goyang-Si 10223, Korea
Kim KH: Department of Architectural Engineering, University of Ulsan, Ulsan 44610, Korea
Kim A: Department of Biology, Amherst College, 220 South Pleasant Street, Amherst, MA 01002, USA [ORCID]
Bae S: Indoor Air Quality Research Center, Korea Institute of Civil Engineering and Building Technology, Goyang-Si 10223, Korea
Cho D: Department of Living and Built Environment Research, Korea Institute of Civil Engineering and Building Technology, Goyang-Si 10223, Korea
Kim KH: Department of Architectural Engineering, University of Ulsan, Ulsan 44610, Korea
Journal Name
Energies
Volume
14
Issue
8
First Page
2299
Year
2021
Publication Date
2021-04-19
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en14082299, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.31767
This Record
External Link

https://doi.org/10.3390/en14082299
Publisher Version
Download
Meta
Record Statistics
Record Views
185
Version History
[v1] (Original Submission)
Apr 19, 2023
Verified by curator on
Apr 19, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.31767
Record Owner
Auto Uploader for LAPSE
Links to Related Works