LAPSE:2023.25308
Published Article
LAPSE:2023.25308
Improving Transient Stability of a Synchronous Generator Using UIPC with a Unified Control Scheme
Saeed Ghafouri, Mohammad Ali Hajiahmadi, Mehdi Firouzi, Gevork B. Gharehpetian, Saleh Mobayen, Paweł Skruch
March 28, 2023
Abstract
In this paper, the Unified Interphase Power Controller (UIPC) is utilized to protect the synchronous generator in case of faults occurring in the transmission system. The UIPC not only maintains the generator’s stability by keeping its load angle within safe operational limits but also prevents high-amplitude currents from flowing through the stator windings. This also allows for more loading on the generator without compromising the system’s stability. Moreover, utilization of the UIPC improves the LVRT capability of the generator by injecting reactive power at the faulted location. Additionally, a novel unified control scheme is proposed for the UIPC that enhances its performance by omitting the necessity of fault detection algorithms. To evaluate the performance of the proposed controller and the efficacy of the UIPC in protecting the synchronous generator under the faults, simulations have been conducted in a MATLAB/Simulink environment. A test grid was developed comprising a synchronous generator, transmission line model, UIPC, and an infinite grid representing the Point of Common Coupling (PCC), and three fault scenarios have been implemented in the transmission system. The comparative analysis of simulation results demonstrates the capability and efficacy of UIPC in isolating the synchronous generator from the faulted location, which in turn not only enhances transient stability of the generator, but also protects generator windings from detrimental faults currents. Moreover, according to the results, UIPC also contributes to recovering the voltage dip of the fault location via injecting reactive power.
Keywords
fault protection, LVRT capability, synchronous generator, transient stability, UIPC
Suggested Citation
Ghafouri S, Hajiahmadi MA, Firouzi M, Gharehpetian GB, Mobayen S, Skruch P. Improving Transient Stability of a Synchronous Generator Using UIPC with a Unified Control Scheme. (2023). LAPSE:2023.25308
Author Affiliations
Ghafouri S: Electrical Engineering Department, Amirkabir University of Technology, Tehran 15916-34311, Iran
Hajiahmadi MA: Electrical Engineering Department, Amirkabir University of Technology, Tehran 15916-34311, Iran
Firouzi M: Department of Electrical Engineering, Abhar Branch, Islamic Azad University, Abhar 45619-34367, Iran
Gharehpetian GB: Electrical Engineering Department, Amirkabir University of Technology, Tehran 15916-34311, Iran [ORCID]
Mobayen S: Department of Electrical Engineering, University of Zanjan, Zanjan 45371-38791, Iran; Future Technology Research Center, National Yunlin University of Science and Technology, 123 University Road, Section 3, Douliou, Yunlin 64002, Taiwan [ORCID]
Skruch P: Department of Automatic Control and Robotics, AGH University of Science and Technology, 30-059 Kraków, Poland
Journal Name
Energies
Volume
15
Issue
16
First Page
6072
Year
2022
Publication Date
2022-08-22
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en15166072, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.25308
This Record
External Link

https://doi.org/10.3390/en15166072
Publisher Version
Download
Files
Mar 28, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
175
Version History
[v1] (Original Submission)
Mar 28, 2023
 
Verified by curator on
Mar 28, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.25308
 
Record Owner
Auto Uploader for LAPSE
Links to Related Works
Directly Related to This Work
Publisher Version

[0.5 s]