LAPSE:2023.22896v1
Published Article

LAPSE:2023.22896v1
The Energy Saving Potential of Wide Windows in Hospital Patient Rooms, Optimizing the Type of Glazing and Lighting Control Strategy under Different Climatic Conditions
March 24, 2023
Abstract
If not properly designed, the adoption of large windows can sometimes have a negative impact on building energy demand. For this reason, aggravated by the outdated building envelope of the healthcare building stock, large fenestration systems are usually avoided in hospitals, especially in old structures. However, with appropriate glazing specifications, the adoption of wider openings can result into significant energy savings, lower costs and strong positive effects on patients and staff well-being. The present study investigates how different window sizes and types of glazing affect heating, cooling and lighting energy demand in a hospital patient room. The objective is to evaluate the energy savings that may be obtained when installing larger windows and to identify the glazing properties allowing one to reach the maximum energy reductions. Simulations were carried out using nine diverse glazing systems, already available on the market, and their energy performance was evaluated in relation to two different window areas: a common size opening, characterized by a 25% Window-to-Wall Ratio (WWR), and a floor to ceiling window, with 77% WWR. The analysis was conducted taking into consideration four different orientations in four Italian cities, supposing two artificial lighting control strategies. The results highlighted how the adoption of wider windows with appropriate glazings and a daylight-linked dimming lighting control strategy may lower the primary energy demand up to 17%.
If not properly designed, the adoption of large windows can sometimes have a negative impact on building energy demand. For this reason, aggravated by the outdated building envelope of the healthcare building stock, large fenestration systems are usually avoided in hospitals, especially in old structures. However, with appropriate glazing specifications, the adoption of wider openings can result into significant energy savings, lower costs and strong positive effects on patients and staff well-being. The present study investigates how different window sizes and types of glazing affect heating, cooling and lighting energy demand in a hospital patient room. The objective is to evaluate the energy savings that may be obtained when installing larger windows and to identify the glazing properties allowing one to reach the maximum energy reductions. Simulations were carried out using nine diverse glazing systems, already available on the market, and their energy performance was evaluated in relation to two different window areas: a common size opening, characterized by a 25% Window-to-Wall Ratio (WWR), and a floor to ceiling window, with 77% WWR. The analysis was conducted taking into consideration four different orientations in four Italian cities, supposing two artificial lighting control strategies. The results highlighted how the adoption of wider windows with appropriate glazings and a daylight-linked dimming lighting control strategy may lower the primary energy demand up to 17%.
Record ID
Keywords
dynamic building energy simulations, energy demand, glazing specifications, hospital patient rooms, lighting, TRNSYS, window-to-wall ratio (WWR)
Subject
Suggested Citation
Cesari S, Valdiserri P, Coccagna M, Mazzacane S. The Energy Saving Potential of Wide Windows in Hospital Patient Rooms, Optimizing the Type of Glazing and Lighting Control Strategy under Different Climatic Conditions. (2023). LAPSE:2023.22896v1
Author Affiliations
Cesari S: Department of Architecture, University of Ferrara, 44121 Ferrara, Italy; CIAS Research Centre for Pollution Control in High Sterility Rooms, Department of Architecture, University of Ferrara, 44122 Ferrara, Italy [ORCID]
Valdiserri P: Department of Industrial Engineering, University of Bologna, 40136 Bologna, Italy [ORCID]
Coccagna M: CIAS Research Centre for Pollution Control in High Sterility Rooms, Department of Architecture, University of Ferrara, 44122 Ferrara, Italy [ORCID]
Mazzacane S: CIAS Research Centre for Pollution Control in High Sterility Rooms, Department of Architecture, University of Ferrara, 44122 Ferrara, Italy
Valdiserri P: Department of Industrial Engineering, University of Bologna, 40136 Bologna, Italy [ORCID]
Coccagna M: CIAS Research Centre for Pollution Control in High Sterility Rooms, Department of Architecture, University of Ferrara, 44122 Ferrara, Italy [ORCID]
Mazzacane S: CIAS Research Centre for Pollution Control in High Sterility Rooms, Department of Architecture, University of Ferrara, 44122 Ferrara, Italy
Journal Name
Energies
Volume
13
Issue
8
Article Number
E2116
Year
2020
Publication Date
2020-04-24
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en13082116, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.22896v1
This Record
External Link

https://doi.org/10.3390/en13082116
Publisher Version
Download
Meta
Record Statistics
Record Views
377
Version History
[v1] (Original Submission)
Mar 24, 2023
Verified by curator on
Mar 24, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.22896v1
Record Owner
Auto Uploader for LAPSE
Links to Related Works
(0.08 seconds)
[0.08 s]