PI Parameter Influence on Underfloor Heating Energy Consumption and Setpoint Tracking in nZEBs
March 24, 2023
Abstract
In rooms with underfloor heating (UFH), local on−off controllers most often regulate the air temperature with poor accuracy and energy penalties. It is known that proportional−integral (PI) controllers can regulate most processes more precisely. However, hydronic UFH systems have long time constants, especially in low-energy buildings, and PI parameters are not easy to set manually. In this work, several potential PI parameter estimation methods were applied, including optimizing the parameters in GenOpt, calculating the parameters based on simplified models, and tuning the parameters automatically in Matlab. For all found parameter combinations, the energy consumption and control precision were evaluated. Simpler methods were compared to the optimal solutions to find similar parameters. Compared with an on−off controller with a 0.5 K dead-band, the best PI parameter combination found was with a proportional gain of 18 and an integration time of 2300 s, which could decrease the energy consumption for heating by 9% and by 5% compared with default PI parameters. Moreover, while GenOpt was the best method to find the optimal parameters, it was also possible with a simple automatic test and calculation within a weekend. The test can be, for example, 6-h setbacks applied during the nights or weekend-long pseudo-random changes in the setpoint signal. The parameters can be calculated based on the simplified model from these tests using any well-known simple method. Results revealed that the UFH PI controller with the correct parameters started to work in a predictive fashion and the resulting room temperature curves were practically ideal.
In rooms with underfloor heating (UFH), local on−off controllers most often regulate the air temperature with poor accuracy and energy penalties. It is known that proportional−integral (PI) controllers can regulate most processes more precisely. However, hydronic UFH systems have long time constants, especially in low-energy buildings, and PI parameters are not easy to set manually. In this work, several potential PI parameter estimation methods were applied, including optimizing the parameters in GenOpt, calculating the parameters based on simplified models, and tuning the parameters automatically in Matlab. For all found parameter combinations, the energy consumption and control precision were evaluated. Simpler methods were compared to the optimal solutions to find similar parameters. Compared with an on−off controller with a 0.5 K dead-band, the best PI parameter combination found was with a proportional gain of 18 and an integration time of 2300 s, which could decrease the energy consumption for heating by 9% and by 5% compared with default PI parameters. Moreover, while GenOpt was the best method to find the optimal parameters, it was also possible with a simple automatic test and calculation within a weekend. The test can be, for example, 6-h setbacks applied during the nights or weekend-long pseudo-random changes in the setpoint signal. The parameters can be calculated based on the simplified model from these tests using any well-known simple method. Results revealed that the UFH PI controller with the correct parameters started to work in a predictive fashion and the resulting room temperature curves were practically ideal.
Record ID
Keywords
building simulation, heat pumps, IDA ICE, intermittent heating, model predictive control (MPC), proportional–integral–derivative (PID) control, thermostats
Subject
Suggested Citation
Kull TM, Thalfeldt M, Kurnitski J. PI Parameter Influence on Underfloor Heating Energy Consumption and Setpoint Tracking in nZEBs. (2023). LAPSE:2023.22854
Author Affiliations
Kull TM: Nearly Zero Energy Buildings Research Group, Tallinn University of Technology, Ehitajate tee 5, 19086 Tallinn, Estonia [ORCID]
Thalfeldt M: Nearly Zero Energy Buildings Research Group, Tallinn University of Technology, Ehitajate tee 5, 19086 Tallinn, Estonia
Kurnitski J: Nearly Zero Energy Buildings Research Group, Tallinn University of Technology, Ehitajate tee 5, 19086 Tallinn, Estonia; Department of Civil Engineering, Rakentajanaukio 4 A, Aalto University, FI-02150 Espoo, Finland [ORCID]
Thalfeldt M: Nearly Zero Energy Buildings Research Group, Tallinn University of Technology, Ehitajate tee 5, 19086 Tallinn, Estonia
Kurnitski J: Nearly Zero Energy Buildings Research Group, Tallinn University of Technology, Ehitajate tee 5, 19086 Tallinn, Estonia; Department of Civil Engineering, Rakentajanaukio 4 A, Aalto University, FI-02150 Espoo, Finland [ORCID]
Journal Name
Energies
Volume
13
Issue
8
Article Number
E2068
Year
2020
Publication Date
2020-04-21
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en13082068, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.22854
This Record
External Link

https://doi.org/10.3390/en13082068
Publisher Version
Download
Meta
Record Statistics
Record Views
445
Version History
[v1] (Original Submission)
Mar 24, 2023
Verified by curator on
Mar 24, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.22854
Record Owner
Auto Uploader for LAPSE
Links to Related Works
(0.09 seconds)
[0.1 s]