LAPSE:2023.11651v1
Published Article
LAPSE:2023.11651v1
Study on Induced Voltage and Circulation Current of Metal Layer in Single-Core Cable of High-Speed Railway Power Transmission Line
Hao Wang, Zhensheng Wu
February 27, 2023
Abstract
The metal shield and metal armor layers of single-core cables on high-speed railroad power penetration lines are usually grounded by common equipment protectors. This grounding method brings a continuous circulating current between the metal shield and metal armor layer compared to the subequipment protection grounding. In order to quantitatively study the circulating current condition of the through line and its influence on the reliability of the railroad power through line, the induced electric potential and circulating current generation mechanism of the single-core cable of the through line and its influencing factors were firstly analyzed in depth. Then, based on the cross-sectional structure of the single-core cable and the location of the traction network and cable in the roadbed section, a traction power supply model was established and simulated for the interlayer-induced potentials and circulating currents due to the two grounding protection methods under no load, single train operation, and heavy load four-train operation of the line. Finally, three actual sections of the Shanghai−Kunming and Nan−Kunming high-speed railroads in China were selected to collect and analyze the loop flow data with no load and with vehicles passing through, and finally the loop flow law of single-core cable for railroad electric through traffic was derived. The analysis shows that when the metal sheath of a single-core cable is grounded by ordinary equipment, the circulating current generated does not exceed 1% of the core current, which meets the relevant safety standards, but the induced voltage in the case of large loads will exceed 50 V safety voltage.
Keywords
high-speed railway, induced voltage, shield protector grounding, single-core cable
Suggested Citation
Wang H, Wu Z. Study on Induced Voltage and Circulation Current of Metal Layer in Single-Core Cable of High-Speed Railway Power Transmission Line. (2023). LAPSE:2023.11651v1
Author Affiliations
Wang H: China Railway First Survey and Design Institute Group Co., Ltd., Xi’an 710043, China
Wu Z: School of Electrical Engineering, Beijing Jiaotong University, Beijing 100044, China
Journal Name
Energies
Volume
15
Issue
14
First Page
5010
Year
2022
Publication Date
2022-07-08
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en15145010, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.11651v1
This Record
External Link

https://doi.org/10.3390/en15145010
Publisher Version
Download
Files
Feb 27, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
179
Version History
[v1] (Original Submission)
Feb 27, 2023
 
Verified by curator on
Feb 27, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.11651v1
 
Record Owner
Auto Uploader for LAPSE
Links to Related Works
Directly Related to This Work
Publisher Version