Abstract
This study used computational fluid dynamics for low greenhouse effect refrigerant (R-513A) simulation analysis in the two-stage 150 USRT class oil-free centrifugal refrigerant compressor using integrated part load value (IPLV) and internal flow field. The compressor rotor speed and mass flow rate for the IPLV working conditions with various loads were planned using Stage 1 and Stage 2 simulations, respectively. The performance and flow field numerical simulation analyses for the two-stage centrifugal compressor is discussed. This study used Ansys-CFX software for numerical simulation analysis and the conservation form of a 3D steady-state Navier−Stokes equation set with the finite volume discretization method for computation. The computing mode produced better computing efficiency and flexible mesh setting using the k-omega (k-ω) model, which has better computational performance in the near wall boundary layer and low Reynolds number flow field (used as the turbulence model) for simulation. The R-513A refrigerant property setting was calculated using the Soave−Redlich−Kwong gas equation. This study discusses the shaft work, pressure ratio, and isentropic efficiency and also describes the main research findings with the meridional pressure, isentropic efficiency contour maps, and flow field velocity vector diagrams. According to the numerical simulation results, in Stage 1 and Stage 2 simulations, the isentropic efficiency produced the highest numerical results in the 75% load case, which are 88.19% and 89.06%, respectively. The isentropic efficiency decreased to 75.93% and 82.26%, respectively, in the 25% load case. The flow field velocity vector diagram shows that in the 25% load case, there was back-flow field distribution near the impeller shroud. The compressor performance was also analyzed.
Keywords
centrifugal compressor, computational fluid dynamics analysis, R-513A refrigerant
Suggested Citation
Hung KS, Hsiao WC, Li YC, Kuan YD. 150USRT Class R-513A Refrigerant Two-Stage Centrifugal Compressor Design Point and Separation Point Flow Field Simulation Analysis. (2023). LAPSE:2023.1133
Author Affiliations
Hung KS: Industrial Technology Research Institute, Green Energy & Environment Research Laboratories, 195, Sec 4, Chung Hsing Rd, Hsinchu 31040, Taiwan
Hsiao WC: Department of Refrigeration, Air Conditioning and Energy Engineering, National Chin-Yi University of Technology, Taichung City 41170, Taiwan
Li YC: Industrial Technology Research Institute, Green Energy & Environment Research Laboratories, 195, Sec 4, Chung Hsing Rd, Hsinchu 31040, Taiwan
Kuan YD: Department of Refrigeration, Air Conditioning and Energy Engineering, National Chin-Yi University of Technology, Taichung City 41170, Taiwan [ORCID]
Journal Name
Processes
Volume
11
Issue
1
First Page
253
Year
2023
Publication Date
2023-01-12
ISSN
2227-9717
Version Comments
Original Submission
Other Meta
PII: pr11010253, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.1133
This Record
External Link

https://doi.org/10.3390/pr11010253
Publisher Version
Download
Files
Feb 21, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
234
Version History
[v1] (Original Submission)
Feb 21, 2023
 
Verified by curator on
Feb 21, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.1133
 
Record Owner
Auto Uploader for LAPSE
Links to Related Works
Directly Related to This Work
Publisher Version