LAPSE:2023.10142
Published Article
LAPSE:2023.10142
Uniformity of Supply Air in the Plenum for Under-Floor Air Distribution Ventilation in a Circular Conference Room: A CFD Study
Xiaolei Fan, Tao Yu, Peng Liu, Xiangdong Li
February 27, 2023
Abstract
Underfloor air distribution (UFAD) systems are increasingly used for their advantages in improving energy savings, indoor air quality, and thermal comfort. In UFAD systems, an underfloor plenum delivers conditioned air to the air supply diffusers. The distribution of internal air velocity and static pressure in plenums determines the uniformity of the airflow to the occupied zones. As a result, the plenum has a detrimental effect on the characteristics of the supply air and, thus, the resulting indoor air quality and thermal comfort. Nevertheless, most existing studies on underfloor plenums focused on small-scale plenums with a single internal air duct. Large plenums and multiple air ducts in UFAD equipped in large premises are underexplored. In this study, a circular underfloor plenum with a large scale (radius of 15 m, height difference of 0.9−2.9 m) and 503 under-seat diffusers in a conference room was studied using computational fluid dynamics (CFD) simulation (ANSYS Fluent (16.0)). The distributions of airflow velocity and static pressure inside the plenum were analyzed and compared to one concentrated air supply mode and three uniform air supply modes. Based on the air velocity at the center of under-seat diffusers, the outgoing airflow uniformity from the diffusers under four cases was evaluated by the index of air velocity uniformity. The results showed that the multiple supply ducts with bottom air outlets yielded the best uniformity of supply air. The findings of this paper are expected to provide a technical basis for realizing the optimal design of the UFAD system in terms of uniformity of supply air.
Keywords
CFD simulation, non-uniformity coefficient, underfloor air distribution, uniform air supply
Suggested Citation
Fan X, Yu T, Liu P, Li X. Uniformity of Supply Air in the Plenum for Under-Floor Air Distribution Ventilation in a Circular Conference Room: A CFD Study. (2023). LAPSE:2023.10142
Author Affiliations
Fan X: Thermal Engineering Department, Shandong Jianzhu University, Jinan 250101, China
Yu T: Thermal Engineering Department, Shandong Jianzhu University, Jinan 250101, China
Liu P: Department of Architecture, Materials, and Structures, SINTEF Community, NO-7465 Trondheim, Norway [ORCID]
Li X: Shandong Provincial Architecture Design & Research Institute Co., Ltd., Jinan 250014, China
Journal Name
Energies
Volume
15
Issue
17
First Page
6370
Year
2022
Publication Date
2022-08-31
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en15176370, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.10142
This Record
External Link

https://doi.org/10.3390/en15176370
Publisher Version
Download
Files
Feb 27, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
157
Version History
[v1] (Original Submission)
Feb 27, 2023
 
Verified by curator on
Feb 27, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.10142
 
Record Owner
Auto Uploader for LAPSE
Links to Related Works
Directly Related to This Work
Publisher Version