Abstract
Exergy-based methods provide engineers with the best information with respect to options for improving the overall thermodynamic efficiency of an energy conversion system. This paper presents the results of an advanced exergy analysis of an air-to-water reversible heat pump whose performance was analyzed with respect to different working fluids. Environmentally deleterious refrigerants, i.e., R410A and R134a (baselines), and their eco-friendly replacements (R290, R152a, R1234ze(E), and R1234yf) were selected. The evaluations were conducted under the same operating conditions (i.e., with the same cooling and heating demands and outdoor temperatures). Based on conventional exergy analysis, it was determined that different priorities should be given for the thermodynamic improvement of the components according to which heating and cooling modes of the system are in use. Therefore, integrated parameters, i.e., the annual values of exergy destruction, were applied for further analysis. The results obtained showed that the heat pump using R410A provided the largest degree of annual exergy destruction estimated on the basis of conventional exergy analysis (5913 kWh), whereas the heat pump using R290 offered the lowest one (4522 kWh). The annual exergy destruction of the R410A cycle with only unavoidable irreversibilities could be decreased by 50%. In this case, compared to R410A and R134a, R152a and R290 provided lower values of the total annual unavoidable aspects of exergy destruction. Considering technological limitations, when removing all the avoidable irreversibilities within the air exchanger, the largest decrease in the total exergy destruction within the system could be reached. The results obtained from the analysis of the removable irreversibilities showed that the mutual interactions between the compressor, evaporator, and condenser were weak. Finally, it was concluded that, from a thermodynamic point of view, the adoption of R152a and R290 in reversible air-to-water heat pumps as replacements for R410A and R134a is advisable.
Keywords
eco-friendly refrigerants, exergetic analysis, exergy destruction, propane, sustainable cooling and heating
Suggested Citation
Voloshchuk V, Gullo P, Nikiforovich E. Advanced Exergy Analysis of Ultra-Low GWP Reversible Heat Pumps for Residential Applications. (2023). LAPSE:2023.6245
Author Affiliations
Voloshchuk V: Department of Energy Processes Automation, National Technical University of Ukraine “Igor Sikorsky Kyiv Polytechnic Institute”, 03056 Kyiv, Ukraine [ORCID]
Gullo P: Department of Mechanical and Electrical Engineering, University of Southern Denmark (SDU), 6400 Sønderborg, Denmark [ORCID]
Nikiforovich E: Department of Nuclear Energy, National Technical University of Ukraine “Igor Sikorsky Kyiv Polytechnic Institute”, 03056 Kyiv, Ukraine
Journal Name
Energies
Volume
16
Issue
2
First Page
703
Year
2023
Publication Date
2023-01-07
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en16020703, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.6245
This Record
External Link

https://doi.org/10.3390/en16020703
Publisher Version
Download
Files
Feb 23, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
419
Version History
[v1] (Original Submission)
Feb 23, 2023
 
Verified by curator on
Feb 23, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.6245
 
Record Owner
Auto Uploader for LAPSE
Links to Related Works
Directly Related to This Work
Publisher Version
(0.07 seconds)

[0.07 s]