LAPSE:2023.36751
Published Article
LAPSE:2023.36751
Experimental Study on Convection and Heat Conduction Heating of an Air-Conditioned Bed System under Winter Lunch Break Mode
Junjie Jin, Peiyao Duan, Yu Liu, Honglin Chen, Tingting Yu
September 21, 2023
In this paper, an experimental study of a system for heating an air-conditioned bed during a 2 h lunch was carried out. The results show that the power consumption of heat conduction heating was only 0.34 kW·h and that the average heat dissipation was 81.3 W, while the power consumption of convection heating was 1.43 kW·h, accompanied by an average heat dissipation of 748.7 W. Regardless of the power consumption or the heat dissipation, the convection heating was significantly higher than the heat conduction heating. As a result, the room air temperature increased from 12.3 °C to 17.3 °C under convection heating, but only increased from 14.4 °C to 15.2 °C under heat conduction heating. The study results indicate that when using heat conduction heating, water temperatures in the range of 38~40 °C could meet the thermal comfort needs of the human body; however, a higher temperature range was required when using convection heating. In contrast, the grade of the hot water required for heat conduction heating was lower. It was also found that the temperature under convection heating rises faster, but it tends to lead to a dry feeling after a long time, while the conductive heating showed a slower temperature rise. There was a cool feeling for 20 min when the heating started, and then the thermal comfort improved. The air-conditioning system in this paper was investigated in a heating experiment in the winter lunch break mode and compared with convection heating. The heat conduction heating resulted in better thermal comfort and higher energy efficiency. It is suggested to adopt the heat conduction heating mode in the winter heating operation of this system.
Keywords
air-conditioned bed system, convection heating, energy conservation, heat conduction heating, thermal comfort
Suggested Citation
Jin J, Duan P, Liu Y, Chen H, Yu T. Experimental Study on Convection and Heat Conduction Heating of an Air-Conditioned Bed System under Winter Lunch Break Mode. (2023). LAPSE:2023.36751
Author Affiliations
Jin J: School of Energy and Building Environmental Engineering, Henan University of Urban Construction, Pingdingshan 467036, China
Duan P: Aviation Engineering Institute, Anyang University, Anyang 455000, China
Liu Y: School of Energy and Building Environmental Engineering, Henan University of Urban Construction, Pingdingshan 467036, China
Chen H: School of Energy and Building Environmental Engineering, Henan University of Urban Construction, Pingdingshan 467036, China
Yu T: School of Energy and Building Environmental Engineering, Henan University of Urban Construction, Pingdingshan 467036, China
Journal Name
Processes
Volume
11
Issue
8
First Page
2391
Year
2023
Publication Date
2023-08-09
Published Version
ISSN
2227-9717
Version Comments
Original Submission
Other Meta
PII: pr11082391, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.36751
This Record
External Link

doi:10.3390/pr11082391
Publisher Version
Download
Files
[Download 1v1.pdf] (17.4 MB)
Sep 21, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
79
Version History
[v1] (Original Submission)
Sep 21, 2023
 