LAPSE:2023.34854v1
Published Article

LAPSE:2023.34854v1
Non-Intrusive Voltage-Inversion Measurement Method for Overhead Transmission Lines Based on Near-End Electric-Field Integration
April 28, 2023
Abstract
Existing electric-field integral inversion methods have limited field application conditions, and they are difficult to arrange electric-field measurement points on high-span overhead lines. This paper proposes a non-intrusive voltage measurement method for overhead transmission lines based on the near-end electric-field integration method. First, the electric-field distribution under 10 kV lines is calculated by finite element simulation software. The electric-field distribution of the plumb line and the discrete integral node below the wire are analyzed. Then, based on traditional electric-field integration, a line-voltage-inversion measurement method based on near-end electric-field integration is proposed. In addition, a voltage-monitoring system based on near-end electric-field integration is constructed. Next, the numerical integration types, the number of integration nodes, and the scale coefficient of the near-end region of the inversion algorithm are optimized with the electric-field simulation data. Finally, to verify the voltage-inversion method proposed in this paper, a test platform for overhead-line voltage is constructed using a MEMS electric-field sensor. The results indicate that the voltage-inversion error is 5.75%. The research results will provide theoretical guidance for non-intrusive voltage-inversion measurement of overhead lines.
Existing electric-field integral inversion methods have limited field application conditions, and they are difficult to arrange electric-field measurement points on high-span overhead lines. This paper proposes a non-intrusive voltage measurement method for overhead transmission lines based on the near-end electric-field integration method. First, the electric-field distribution under 10 kV lines is calculated by finite element simulation software. The electric-field distribution of the plumb line and the discrete integral node below the wire are analyzed. Then, based on traditional electric-field integration, a line-voltage-inversion measurement method based on near-end electric-field integration is proposed. In addition, a voltage-monitoring system based on near-end electric-field integration is constructed. Next, the numerical integration types, the number of integration nodes, and the scale coefficient of the near-end region of the inversion algorithm are optimized with the electric-field simulation data. Finally, to verify the voltage-inversion method proposed in this paper, a test platform for overhead-line voltage is constructed using a MEMS electric-field sensor. The results indicate that the voltage-inversion error is 5.75%. The research results will provide theoretical guidance for non-intrusive voltage-inversion measurement of overhead lines.
Record ID
Keywords
electric-field integration method, non-intrusive voltage measurement, overhead line, voltage-inversion measurement
Suggested Citation
Liao W, Yang Q, Ke K, Qiu Z, Lei Y, Jiao F. Non-Intrusive Voltage-Inversion Measurement Method for Overhead Transmission Lines Based on Near-End Electric-Field Integration. (2023). LAPSE:2023.34854v1
Author Affiliations
Liao W: State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, Chongqing 400044, China
Yang Q: State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, Chongqing 400044, China
Ke K: State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, Chongqing 400044, China
Qiu Z: State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, Chongqing 400044, China
Lei Y: China Electric Power Research Institute, Beijing 100192, China
Jiao F: China Electric Power Research Institute, Beijing 100192, China
Yang Q: State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, Chongqing 400044, China
Ke K: State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, Chongqing 400044, China
Qiu Z: State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University, Chongqing 400044, China
Lei Y: China Electric Power Research Institute, Beijing 100192, China
Jiao F: China Electric Power Research Institute, Beijing 100192, China
Journal Name
Energies
Volume
16
Issue
8
First Page
3415
Year
2023
Publication Date
2023-04-13
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en16083415, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.34854v1
This Record
External Link

https://doi.org/10.3390/en16083415
Publisher Version
Download
Meta
Record Statistics
Record Views
734
Version History
[v1] (Original Submission)
Apr 28, 2023
Verified by curator on
Apr 28, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.34854v1
Record Owner
Auto Uploader for LAPSE
Links to Related Works
(0.09 seconds)
[0.09 s]