LAPSE:2023.32835
Published Article
LAPSE:2023.32835
A Practical GERI-Based Method for Identifying Multiple Erroneous Parameters and Measurements Simultaneously
Ruipeng Guo, Lilan Dong, Hao Wu, Fangdi Hou, Chen Fang
April 20, 2023
Even with modern smart metering systems, erroneous measurements of the real and reactive power in the power system are unavoidable. Multiple erroneous parameters and measurements may occur simultaneously in the state estimation of a bulk power system. This paper proposes a gross error reduction index (GERI)-based method as an additional module for existing state estimators in order to identify multiple erroneous parameters and measurements simultaneously. The measurements are acquired from a supervisory control and data acquisition system and mainly include voltage amplitudes, branch current amplitudes, active power flow, and reactive power flow. This method uses a structure consisting of nested two loops. First, gross errors and the GERI indexes are calculated in the inner loop. Second, the GERI indexes are compared and the maximum GERI in each inner loop is associated with the most suspicious parameter or measurement. Third, when the maximum GERI is less than a given threshold in the outer loop, its corresponding erroneous parameter or measurement is identified. Multiple measurement scans are also adopted in order to increase the redundancy of measurements and the observability of parameters. It should be noted that the proposed algorithm can be directly integrated into the Weighted Least Square estimator. Furthermore, using a faster simplified calculation technique with Givens rotations reduces the required computer memory and increases the computation speed. This method has been demonstrated in the IEEE 14-bus test system and several matpower cases. Due to its outstanding practical performance, it is now used at six provincial power control centers in the Eastern Grid of China.
Keywords
erroneous parameters and measurements, error identification, gross error reduction-index-based method, multiple measurement scans, power system state estimation
Suggested Citation
Guo R, Dong L, Wu H, Hou F, Fang C. A Practical GERI-Based Method for Identifying Multiple Erroneous Parameters and Measurements Simultaneously. (2023). LAPSE:2023.32835
Author Affiliations
Guo R: College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China [ORCID]
Dong L: College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China [ORCID]
Wu H: College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China [ORCID]
Hou F: College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China
Fang C: Electric Power Research Institute, State Grid Shanghai Municipal Electric Power Company, Shanghai 200437, China
Journal Name
Energies
Volume
14
Issue
12
First Page
3390
Year
2021
Publication Date
2021-06-08
Published Version
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en14123390, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.32835
This Record
External Link

doi:10.3390/en14123390
Publisher Version
Download
Files
[Download 1v1.pdf] (6.4 MB)
Apr 20, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
88
Version History
[v1] (Original Submission)
Apr 20, 2023
 
Verified by curator on
Apr 20, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.32835
 
Original Submitter
Auto Uploader for LAPSE
Links to Related Works
Directly Related to This Work
Publisher Version