LAPSE:2023.21603
Published Article

LAPSE:2023.21603
Relation Between Mean Fluid Temperature and Outlet Temperature for Single U-Tube Boreholes
March 22, 2023
Abstract
Ground-coupled heat pump (GCHP) systems usually utilize buried vertical heat exchangers, named borehole heat exchangers (BHEs). The accurate design or simulation of a GCHP system requires the calculation of the time-dependent outlet temperature from the BHEs, Tout. However, the most widely employed BHE simulation models yield the time evolution either of the mean temperature of the BHE-ground surface, Tsm, or of that of the fluid, Tfm. In transient regime, it is not easy to relate Tout to either Tsm or Tfm. In this paper we determine, through 3D finite element simulations, simple expressions of a dimensionless coefficient φ allowing the calculation of Tout by means of a simulation model that yields Tfm. These expressions hold for single U-tube BHEs, both in quasi-steady and in unsteady working conditions. We validate our 3D simulation code by comparison with an analytical BHE model. Then, we present applications of our expressions of φ to calculate the time-dependent values of Tout through a BHE model that yields those of Tfm. Finally, we show that the values of φ in quasi-steady working conditions can be used for a simple calculation of the effective borehole thermal resistance.
Ground-coupled heat pump (GCHP) systems usually utilize buried vertical heat exchangers, named borehole heat exchangers (BHEs). The accurate design or simulation of a GCHP system requires the calculation of the time-dependent outlet temperature from the BHEs, Tout. However, the most widely employed BHE simulation models yield the time evolution either of the mean temperature of the BHE-ground surface, Tsm, or of that of the fluid, Tfm. In transient regime, it is not easy to relate Tout to either Tsm or Tfm. In this paper we determine, through 3D finite element simulations, simple expressions of a dimensionless coefficient φ allowing the calculation of Tout by means of a simulation model that yields Tfm. These expressions hold for single U-tube BHEs, both in quasi-steady and in unsteady working conditions. We validate our 3D simulation code by comparison with an analytical BHE model. Then, we present applications of our expressions of φ to calculate the time-dependent values of Tout through a BHE model that yields those of Tfm. Finally, we show that the values of φ in quasi-steady working conditions can be used for a simple calculation of the effective borehole thermal resistance.
Record ID
Keywords
borehole heat exchangers, effective borehole thermal resistance, ground heat exchangers, ground-coupled heat pumps, outlet temperature, single U-tube
Subject
Suggested Citation
Jahanbin A, Naldi C, Zanchini E. Relation Between Mean Fluid Temperature and Outlet Temperature for Single U-Tube Boreholes. (2023). LAPSE:2023.21603
Author Affiliations
Jahanbin A: Department of Industrial Engineering, Alma Mater Studiorum University of Bologna, Viale Risorgimento 2, 40136 Bologna, Italy [ORCID]
Naldi C: Department of Industrial Engineering, Alma Mater Studiorum University of Bologna, Viale Risorgimento 2, 40136 Bologna, Italy
Zanchini E: Department of Industrial Engineering, Alma Mater Studiorum University of Bologna, Viale Risorgimento 2, 40136 Bologna, Italy
Naldi C: Department of Industrial Engineering, Alma Mater Studiorum University of Bologna, Viale Risorgimento 2, 40136 Bologna, Italy
Zanchini E: Department of Industrial Engineering, Alma Mater Studiorum University of Bologna, Viale Risorgimento 2, 40136 Bologna, Italy
Journal Name
Energies
Volume
13
Issue
4
Article Number
E828
Year
2020
Publication Date
2020-02-14
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en13040828, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.21603
This Record
External Link

https://doi.org/10.3390/en13040828
Publisher Version
Download
Meta
Record Statistics
Record Views
138
Version History
[v1] (Original Submission)
Mar 22, 2023
Verified by curator on
Mar 22, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.21603
Record Owner
Auto Uploader for LAPSE
Links to Related Works
(1.3 seconds) 0.16 + 0.15 + 0.65 + 0.09 + 0 + 0.09 + 0.04 + 0 + 0.04 + 0.08 + 0 + 0