Impact of the Evaporation Temperature on the Air Drying Rate for a Finned Heat Exchanger
March 17, 2023
Abstract
This paper presents the thermal calculations of an air-finned heat exchanger working at temperatures above zero degrees and their verification through testing on a real device. Then, on the basis of the calculations, the influence of evaporation temperature on the drying rate of the constant speed of air flowing through the exchanger was analysed. A quantitative analysis of the effect of the temperature difference between the air being dried and the evaporator on the acceleration of the process was performed. For the analysed case, the same water mass (condensate) can be obtained for an evaporation temperature of 0 °C almost four times faster than for 10 °C. To compare temperature cases, the SMER (specific moisture evaporation ratio) was calculated, which allowed the systems to be compared in terms of energy consumption. The theoretical analysis showed that by reducing the boiling point by 10 degrees, we could increase the SMER from 0.51 kgh20/kWh to 2.18 kgh20/kWh. After receiving the experimental results and including the efficiency of the system, these values were, respectively, 0.44 ± 0.01 kgh20/kWh and 1.91 ± 0.06 kgh20/kWh.
This paper presents the thermal calculations of an air-finned heat exchanger working at temperatures above zero degrees and their verification through testing on a real device. Then, on the basis of the calculations, the influence of evaporation temperature on the drying rate of the constant speed of air flowing through the exchanger was analysed. A quantitative analysis of the effect of the temperature difference between the air being dried and the evaporator on the acceleration of the process was performed. For the analysed case, the same water mass (condensate) can be obtained for an evaporation temperature of 0 °C almost four times faster than for 10 °C. To compare temperature cases, the SMER (specific moisture evaporation ratio) was calculated, which allowed the systems to be compared in terms of energy consumption. The theoretical analysis showed that by reducing the boiling point by 10 degrees, we could increase the SMER from 0.51 kgh20/kWh to 2.18 kgh20/kWh. After receiving the experimental results and including the efficiency of the system, these values were, respectively, 0.44 ± 0.01 kgh20/kWh and 1.91 ± 0.06 kgh20/kWh.
Record ID
Keywords
drying, evaporator, finned heat exchanger, heat exchanger, heat pump, SMER
Subject
Suggested Citation
Mołczan T, Cyklis P. Impact of the Evaporation Temperature on the Air Drying Rate for a Finned Heat Exchanger. (2023). LAPSE:2023.20203
Author Affiliations
Journal Name
Energies
Volume
16
Issue
5
First Page
2132
Year
2023
Publication Date
2023-02-22
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en16052132, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.20203
This Record
External Link

https://doi.org/10.3390/en16052132
Publisher Version
Download
Meta
Record Statistics
Record Views
260
Version History
[v1] (Original Submission)
Mar 17, 2023
Verified by curator on
Mar 17, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.20203
Record Owner
Auto Uploader for LAPSE
Links to Related Works
(0.09 seconds)
[0.1 s]