LAPSE:2023.19424
Published Article

LAPSE:2023.19424
Non-Contact High Voltage Measurement in the Online Partial Discharge Monitoring System
March 9, 2023
Abstract
The article presents an innovative system for non-contact high voltage (HV) measurement, which extends the measurement capabilities of a portable partial discharges (PD) monitoring system intended for diagnostics of power transformers. The proposed method and the developed measuring system are based on the use of a capacitive probe, thanks to which the high voltage measurement is safe (galvanic separation from the objects at ahigh potential). It is also flexible because the voltage ratio of this system can be configured in a wide range by changing the probe’s position. The proposed solution makes the portable PD monitoring system fully autonomous and independent of the substation systems and devices. The article presents both the concept of the non-contact HV measurement system and its practical implementation. The procedure for determining the voltage ratio and measurement uncertainty, which is at an acceptable level of 1−5% in laboratory conditions, was discussed in detail. In addition, the article discusses the digital filtering and wavelet de-noising methods implemented in the software of the monitoring system, which makes it possible to measure the voltage in the presence of strong electromagnetic disturbances occurring at the substation. Finally, the results of field tests carried out on a 250 MVA power transformer are presented, which confirmed the high accuracy of the HV measurement using a capacitive probe and the advantages of this technique.
The article presents an innovative system for non-contact high voltage (HV) measurement, which extends the measurement capabilities of a portable partial discharges (PD) monitoring system intended for diagnostics of power transformers. The proposed method and the developed measuring system are based on the use of a capacitive probe, thanks to which the high voltage measurement is safe (galvanic separation from the objects at ahigh potential). It is also flexible because the voltage ratio of this system can be configured in a wide range by changing the probe’s position. The proposed solution makes the portable PD monitoring system fully autonomous and independent of the substation systems and devices. The article presents both the concept of the non-contact HV measurement system and its practical implementation. The procedure for determining the voltage ratio and measurement uncertainty, which is at an acceptable level of 1−5% in laboratory conditions, was discussed in detail. In addition, the article discusses the digital filtering and wavelet de-noising methods implemented in the software of the monitoring system, which makes it possible to measure the voltage in the presence of strong electromagnetic disturbances occurring at the substation. Finally, the results of field tests carried out on a 250 MVA power transformer are presented, which confirmed the high accuracy of the HV measurement using a capacitive probe and the advantages of this technique.
Record ID
Keywords
capacitive probe, high voltage measurement, non-contact measurement, partial discharge (PD), power transformer monitoring
Subject
Suggested Citation
Walczak K, Sikorski W. Non-Contact High Voltage Measurement in the Online Partial Discharge Monitoring System. (2023). LAPSE:2023.19424
Author Affiliations
Journal Name
Energies
Volume
14
Issue
18
First Page
5777
Year
2021
Publication Date
2021-09-14
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en14185777, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.19424
This Record
External Link

https://doi.org/10.3390/en14185777
Publisher Version
Download
Meta
Record Statistics
Record Views
157
Version History
[v1] (Original Submission)
Mar 9, 2023
Verified by curator on
Mar 9, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.19424
Record Owner
Auto Uploader for LAPSE
Links to Related Works
(1.19 seconds) 0.09 + 0.11 + 0.5 + 0.26 + 0 + 0.05 + 0.06 + 0 + 0.06 + 0.03 + 0 + 0.01