Indoor Comfort, Thermal Indices, and Energy Assessment of Multi-Family Colonial Revival Style Buildings
March 6, 2023
Abstract
Colonial Revival style residences have unique architectural features amongst others. They are common multi-family residences in the United States with no or limited information about their performance. The research purpose is to assess indoor comfort, energy performance, and thermal indices in multi-family Colonial Revival style residences. The research questions include (i) Do Colonial Revival style buildings perform better than other old buildings? (ii) Do the buildings consume additional electricity than typical and other old buildings? The research examined four case studies in Hartford County, Connecticut. The investigation explored comfort surveys, monitoring, collection of actual electricity usage, and assessed thermal indices using mathematical models. The average indoor temperature of 25.4 °C and relative humidity (RH) of 61.3% are reported. About 67% of the residents are thermally comfortable. The research noted significance between thermal sensation and other variables, excluding how occupants feel about the air movement. The average number of hours of temperature exceeds 28.0 °C and 30.0 °C marks for over 11.4% and 2.5% of the time, respectively, except in one of the buildings. The mean indoor temperatures are within the applicable bands of the adaptive comfort models. The averages of actual thermal sensation vote (TSV) ranged from 3.32 to 4.37 on a 7-point sensation scale. The mean neutral temperatures varied from 24.2−25.6 °C. The average monthly electricity bill is within the national average for residences in summer, excluding in August. The mean wet-bulb globe temperature (WBGT) of 21.1−22.3 °C and summer simmer index (SSI) of 30.1−32.4 °C are calculated as feasible bands for thermal indices in the buildings. The basements are more comfortable than other spaces within the case studies. The research outcomes can be used for future developments of Colonial Revival style and other similar buildings. The study recommends interventions such as retrofit to improve the performance of some existing Colonial Revival style buildings, especially the older ones that are less insulated with outdated equipment and appliances.
Colonial Revival style residences have unique architectural features amongst others. They are common multi-family residences in the United States with no or limited information about their performance. The research purpose is to assess indoor comfort, energy performance, and thermal indices in multi-family Colonial Revival style residences. The research questions include (i) Do Colonial Revival style buildings perform better than other old buildings? (ii) Do the buildings consume additional electricity than typical and other old buildings? The research examined four case studies in Hartford County, Connecticut. The investigation explored comfort surveys, monitoring, collection of actual electricity usage, and assessed thermal indices using mathematical models. The average indoor temperature of 25.4 °C and relative humidity (RH) of 61.3% are reported. About 67% of the residents are thermally comfortable. The research noted significance between thermal sensation and other variables, excluding how occupants feel about the air movement. The average number of hours of temperature exceeds 28.0 °C and 30.0 °C marks for over 11.4% and 2.5% of the time, respectively, except in one of the buildings. The mean indoor temperatures are within the applicable bands of the adaptive comfort models. The averages of actual thermal sensation vote (TSV) ranged from 3.32 to 4.37 on a 7-point sensation scale. The mean neutral temperatures varied from 24.2−25.6 °C. The average monthly electricity bill is within the national average for residences in summer, excluding in August. The mean wet-bulb globe temperature (WBGT) of 21.1−22.3 °C and summer simmer index (SSI) of 30.1−32.4 °C are calculated as feasible bands for thermal indices in the buildings. The basements are more comfortable than other spaces within the case studies. The research outcomes can be used for future developments of Colonial Revival style and other similar buildings. The study recommends interventions such as retrofit to improve the performance of some existing Colonial Revival style buildings, especially the older ones that are less insulated with outdated equipment and appliances.
Record ID
Keywords
colonial revival style buildings, energy assessment, neutral temperature, on-site measurements, overheating, predicted mean vote, thermal comfort, thermal indices
Subject
Suggested Citation
Adekunle TO. Indoor Comfort, Thermal Indices, and Energy Assessment of Multi-Family Colonial Revival Style Buildings. (2023). LAPSE:2023.17500
Author Affiliations
Adekunle TO: Department of Architecture, College of Engineering, Technology, and Architecture (CETA), University of Hartford, West Hartford, CT 06117, USA [ORCID]
Journal Name
Energies
Volume
14
Issue
22
First Page
7468
Year
2021
Publication Date
2021-11-09
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en14227468, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.17500
This Record
External Link

https://doi.org/10.3390/en14227468
Publisher Version
Download
Meta
Record Statistics
Record Views
155
Version History
[v1] (Original Submission)
Mar 6, 2023
Verified by curator on
Mar 6, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.17500
Record Owner
Auto Uploader for LAPSE
Links to Related Works
[0.58 s]