Numerical Feasibility Study of Self-Regulating Radiant Ceiling in Combination with Diffuse Ceiling Ventilation
March 2, 2023
Abstract
A focus on indoor comfort and tightening targets for energy savings in buildings presents new opportunities for heating, ventilation, and air-conditioning products (HVAC). This paper presents a novel comfort solution that integrates a suspended radiant ceiling with diffuse ventilation, dubbed HVACeiling. In combination with the concrete slab, the HVACeiling has the potential to provide thermal comfort with minimal temperature offset, which supports operation of the heating and cooling system at temperatures very close to the room comfort temperature. The paper presents a parametric numerical study of the concept in a simplified two-pipe layout with fixed flow and fixed temperatures. First, the analysis was focused on different internal and solar loads, heat losses, and climatic locations with the aim of assessing the potential of self-regulation, i.e., no active controls, thermal comfort, ability to reduce peak loads and the consequential building design considerations. Secondly, the purpose was to analyse the concept in a generic office building with five offices and one meeting room and compare it to other HVAC solutions. The whole-year analyses of heating, cooling, energy performance, and thermal comfort were done using the building performance simulation software IDA ICE. It was found that it was possible to create thermal comfort in Paris, Munich, and Copenhagen with water circulating constantly with fixed temperatures of 20−24 °C without controls and with window sizes from 15 to 30% of the floor area. The studies showed that the HVACeiling reduced the operative peak temperatures on the warmest days in comparison with a standard radiant ceiling with mixing ventilation by 1 K. Compared to all-air solutions, the HVACeiling reduced the yearly energy consumption by 20−30% and the peak power in summer up to 69%. This study indicates that thermal comfort is achievable in a European context even at very small temperature offsets, which supports the use of more renewable energy sources.
A focus on indoor comfort and tightening targets for energy savings in buildings presents new opportunities for heating, ventilation, and air-conditioning products (HVAC). This paper presents a novel comfort solution that integrates a suspended radiant ceiling with diffuse ventilation, dubbed HVACeiling. In combination with the concrete slab, the HVACeiling has the potential to provide thermal comfort with minimal temperature offset, which supports operation of the heating and cooling system at temperatures very close to the room comfort temperature. The paper presents a parametric numerical study of the concept in a simplified two-pipe layout with fixed flow and fixed temperatures. First, the analysis was focused on different internal and solar loads, heat losses, and climatic locations with the aim of assessing the potential of self-regulation, i.e., no active controls, thermal comfort, ability to reduce peak loads and the consequential building design considerations. Secondly, the purpose was to analyse the concept in a generic office building with five offices and one meeting room and compare it to other HVAC solutions. The whole-year analyses of heating, cooling, energy performance, and thermal comfort were done using the building performance simulation software IDA ICE. It was found that it was possible to create thermal comfort in Paris, Munich, and Copenhagen with water circulating constantly with fixed temperatures of 20−24 °C without controls and with window sizes from 15 to 30% of the floor area. The studies showed that the HVACeiling reduced the operative peak temperatures on the warmest days in comparison with a standard radiant ceiling with mixing ventilation by 1 K. Compared to all-air solutions, the HVACeiling reduced the yearly energy consumption by 20−30% and the peak power in summer up to 69%. This study indicates that thermal comfort is achievable in a European context even at very small temperature offsets, which supports the use of more renewable energy sources.
Record ID
Keywords
cooling, diffuse ventilation, energy saving, heating, radiant ceilings
Suggested Citation
Krusaa MR, Hviid CA. Numerical Feasibility Study of Self-Regulating Radiant Ceiling in Combination with Diffuse Ceiling Ventilation. (2023). LAPSE:2023.15259
Author Affiliations
Krusaa MR: Department of Civil Engineering, Technical University of Denmark, Brovej, Building 118, DK-2800 Kgs. Lyngby, Denmark; Saint-Gobain Nordic A/S, Robert Jacobsensvej 62A, DK-2300 København, Denmark
Hviid CA: Department of Civil Engineering, Technical University of Denmark, Brovej, Building 118, DK-2800 Kgs. Lyngby, Denmark [ORCID]
Hviid CA: Department of Civil Engineering, Technical University of Denmark, Brovej, Building 118, DK-2800 Kgs. Lyngby, Denmark [ORCID]
Journal Name
Energies
Volume
15
Issue
4
First Page
1319
Year
2022
Publication Date
2022-02-11
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en15041319, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.15259
This Record
External Link

https://doi.org/10.3390/en15041319
Publisher Version
Download
Meta
Record Statistics
Record Views
157
Version History
[v1] (Original Submission)
Mar 2, 2023
Verified by curator on
Mar 2, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.15259
Record Owner
Auto Uploader for LAPSE
Links to Related Works
(0.37 seconds)