Diagnostics on the Basis of the Frequency-Temperature Dependences of the Loss Angle Tangent of Heavily Moistured Oil-Impregnated Pressboard
March 1, 2023
Abstract
The aim of this study was to perform precision measurements of the frequency-temperature dependences of the loss angle tangent of the liquid-solid composite with the FDS Dirana meter. The composite consisted of heavily moistered oil-impregnated pressboard. The moisturization of the pressboard occurred in a manner as close as possible to the process of wetting the insulation in power transformers to a moisture content of (5.0 ± 0.2) wt. %. This value of moisture content was chosen because exceeding this value can lead to transformer failure. The measuring temperature range was from 293.15 K (20 °C) to 333.15 K (60 °C), with a step of 8 K. The measuring frequency range was 0.0001 Hz to 5000 Hz. It was observed that the shape of the frequency dependence of the loss angle tangent for a moisture content of 5.0 wt. % does not depend on the value of the measuring temperature. An increase in temperature leads to a shift of the waveforms into the higher frequency region. This is associated with a decrease in the relaxation time, and its value depends on the activation energy. It was found that a good fit of the waveforms, simulated by Dirana, to the actual tgδ waveforms obtained at temperatures between 293.15 K (20 °C) and 333.15 K (60 °C) requires the introduction of temperatures, higher than the actual insulation temperatures, into the program. It was found that estimating the moisture content for different temperatures using Dirana soft-ware for insulating an oil-impregnated pressboard produced large discrepancies from the actual content. Better results were obtained after an adjustment requiring manual temperature correction towards higher, compared to measured, temperatures. The moisture content estimated after correction by the Dirana meter ranges from of 4.5 wt. % to 5.7 wt. % and increases almost linearly with increasing measuring temperature. The average moisture content estimated by the Dirana meter for all measuring temperatures is 5.1 wt. % and is close to the actual content (5.0 ± 0.2) wt. %. The uncertainty of the estimate is ±0.43 wt. % and is more than twice as high as the true value.
The aim of this study was to perform precision measurements of the frequency-temperature dependences of the loss angle tangent of the liquid-solid composite with the FDS Dirana meter. The composite consisted of heavily moistered oil-impregnated pressboard. The moisturization of the pressboard occurred in a manner as close as possible to the process of wetting the insulation in power transformers to a moisture content of (5.0 ± 0.2) wt. %. This value of moisture content was chosen because exceeding this value can lead to transformer failure. The measuring temperature range was from 293.15 K (20 °C) to 333.15 K (60 °C), with a step of 8 K. The measuring frequency range was 0.0001 Hz to 5000 Hz. It was observed that the shape of the frequency dependence of the loss angle tangent for a moisture content of 5.0 wt. % does not depend on the value of the measuring temperature. An increase in temperature leads to a shift of the waveforms into the higher frequency region. This is associated with a decrease in the relaxation time, and its value depends on the activation energy. It was found that a good fit of the waveforms, simulated by Dirana, to the actual tgδ waveforms obtained at temperatures between 293.15 K (20 °C) and 333.15 K (60 °C) requires the introduction of temperatures, higher than the actual insulation temperatures, into the program. It was found that estimating the moisture content for different temperatures using Dirana soft-ware for insulating an oil-impregnated pressboard produced large discrepancies from the actual content. Better results were obtained after an adjustment requiring manual temperature correction towards higher, compared to measured, temperatures. The moisture content estimated after correction by the Dirana meter ranges from of 4.5 wt. % to 5.7 wt. % and increases almost linearly with increasing measuring temperature. The average moisture content estimated by the Dirana meter for all measuring temperatures is 5.1 wt. % and is close to the actual content (5.0 ± 0.2) wt. %. The uncertainty of the estimate is ±0.43 wt. % and is more than twice as high as the true value.
Record ID
Keywords
FDS method, insulation of transformers, moisture, oil, oil-impregnated pressboard, transformer diagnostics, transformer temperature
Subject
Suggested Citation
Kołtunowicz TN, Kierczynski K, Okal P, Patryn A, Gutten M. Diagnostics on the Basis of the Frequency-Temperature Dependences of the Loss Angle Tangent of Heavily Moistured Oil-Impregnated Pressboard. (2023). LAPSE:2023.14026
Author Affiliations
Kołtunowicz TN: Department of Electrical Devices High Voltage Technology, Faculty of Electrical Engineering Computer Science, Lublin University of Technology, 38A, Nadbystrzycka Str., 20-618 Lublin, Poland [ORCID]
Kierczynski K: Department of Electrical Devices High Voltage Technology, Faculty of Electrical Engineering Computer Science, Lublin University of Technology, 38A, Nadbystrzycka Str., 20-618 Lublin, Poland [ORCID]
Okal P: Department of Electrical Devices High Voltage Technology, Faculty of Electrical Engineering Computer Science, Lublin University of Technology, 38A, Nadbystrzycka Str., 20-618 Lublin, Poland
Patryn A: Department of Electronics, Faculty of Electronics and Computer Science, Koszalin University of Technology, 2, Sniadeckich Str., 75-453 Koszalin, Poland [ORCID]
Gutten M: Department of Measurement and Application Electrical Engineering, University of Zilina, 8215/1 Univerzitná, 01026 Zilina, Slovakia
Kierczynski K: Department of Electrical Devices High Voltage Technology, Faculty of Electrical Engineering Computer Science, Lublin University of Technology, 38A, Nadbystrzycka Str., 20-618 Lublin, Poland [ORCID]
Okal P: Department of Electrical Devices High Voltage Technology, Faculty of Electrical Engineering Computer Science, Lublin University of Technology, 38A, Nadbystrzycka Str., 20-618 Lublin, Poland
Patryn A: Department of Electronics, Faculty of Electronics and Computer Science, Koszalin University of Technology, 2, Sniadeckich Str., 75-453 Koszalin, Poland [ORCID]
Gutten M: Department of Measurement and Application Electrical Engineering, University of Zilina, 8215/1 Univerzitná, 01026 Zilina, Slovakia
Journal Name
Energies
Volume
15
Issue
8
First Page
2924
Year
2022
Publication Date
2022-04-15
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en15082924, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.14026
This Record
External Link

https://doi.org/10.3390/en15082924
Publisher Version
Download
Meta
Record Statistics
Record Views
165
Version History
[v1] (Original Submission)
Mar 1, 2023
Verified by curator on
Mar 1, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.14026
Record Owner
Auto Uploader for LAPSE
Links to Related Works
(0.77 seconds)