LAPSE:2023.13191
Published Article
LAPSE:2023.13191
Min-Max Regret-Based Approach for Sizing and Placement of DGs in Distribution System under a 24 h Load Horizon
Asad Abbas, Saeed Mian Qaisar, Asad Waqar, Nasim Ullah, Ahmad Aziz Al Ahmadi
February 28, 2023
Abstract
Load variations in any power system result in loss escalation and voltage drops. With the sensible and optimal allocation of distributed generators (DGs), these problems could be considerably mitigated. It has been seen in existing methods that, ideally, the allocation of DGs has been carried out during fixed loads and constant power requirements. However, in real scenarios the loads are always variable and the allocation of DGs must be done in accordance with the variations of the connected load. Therefore, the current paper addresses the aforementioned problem by the distinctive optimal allocation of DGs for each variability of 24 h load horizon. However, a single exclusive solution is considered among all allocations of 24 h. The min-max regret concept has been utilized in order to deal with such a methodology. Altogether, 24 scenarios are analyzed wherein each scenario corresponds to a specific hour of the respective day. The optimal allocation of DGs in terms of their optimal sizing and placement has been carried out by using three algorithms including battle royale optimization (BRO), accelerated particle swarm optimization (APSO), and genetic algorithm (GA). The multi-objective optimization problem is evaluated on the basis of minimum value criterion of the multi-objective index (MO). MO comprises active and reactive power losses and voltage deviation. Hence, in order to find the robustness of the proposed technique, Conseil international des grands reseaux electriques’ (CIGRE) MV benchmark model incorporating 14 buses has been used considerably as a test network. In the end, the results of three proposed algorithms have been compared.
Keywords
battle royale optimization, DGs’ allocation, distributed generators, min-max regret criteria, power losses, sizes and locations of DGs
Suggested Citation
Abbas A, Qaisar SM, Waqar A, Ullah N, Al Ahmadi AA. Min-Max Regret-Based Approach for Sizing and Placement of DGs in Distribution System under a 24 h Load Horizon. (2023). LAPSE:2023.13191
Author Affiliations
Abbas A: Department of Electrical Engineering, Chungnam National University, Daejeon 34134, Korea [ORCID]
Qaisar SM: College of Engineering, Effat University, Jeddah 22332, Saudi Arabia; Communication and Signal Processing Lab, Energy and Technology Center, Effat University, Jeddah 22332, Saudi Arabia
Waqar A: Department of Electrical Engineering, Bahria University, Islamabad 44000, Pakistan [ORCID]
Ullah N: Department of Electrical Engineering, College of Engineering, Taif University, Taif 21944, Saudi Arabia [ORCID]
Al Ahmadi AA: Department of Electrical Engineering, College of Engineering, Taif University, Taif 21944, Saudi Arabia
Journal Name
Energies
Volume
15
Issue
10
First Page
3701
Year
2022
Publication Date
2022-05-18
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en15103701, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2023.13191
This Record
External Link

https://doi.org/10.3390/en15103701
Publisher Version
Download
Files
Feb 28, 2023
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
252
Version History
[v1] (Original Submission)
Feb 28, 2023
 
Verified by curator on
Feb 28, 2023
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2023.13191
 
Record Owner
Auto Uploader for LAPSE
Links to Related Works
Directly Related to This Work
Publisher Version