LAPSE:2019.0760
Published Article
LAPSE:2019.0760
Integration of Lithium-Ion Battery Storage Systems in Hydroelectric Plants for Supplying Primary Control Reserve
Fabio Bignucolo, Roberto Caldon, Massimiliano Coppo, Fabio Pasut, Martino Pettinà
July 26, 2019
The ever-growing diffusion of renewables as electrical generation sources is forcing the electrical power system to face new and challenging regulation problems to preserve grid stability. Among these, the primary control reserve is reckoned to be one of the most important issues, since the introduction of generators based on renewable energies and interconnected through static converters, if relieved from the primary reserve contribution, reduces both the system inertia and the available power reserve in case of network events involving frequency perturbations. In this scenario, renewable plants such as hydroelectric run-of-river generators could be required to provide the primary control reserve ancillary service. In this paper, the integration between a multi-unit run-of-river power plant and a lithium-ion based battery storage system is investigated, suitably accounting for the ancillary service characteristics as required by present grid codes. The storage system is studied in terms of maximum economic profitability, taking into account its operating constraints. Dynamic simulations are carried out within the DIgSILENT PowerFactory 2016 software environment in order to analyse the plant response in case of network frequency contingencies, comparing the pure hydroelectric plant with the hybrid one, in which the primary reserve is partially or completely supplied by the storage system. Results confirm that the battery storage system response to frequency perturbations is clearly faster and more accurate during the transient phase compared to a traditional plant, since time delays due to hydraulic and mechanical regulations are overpassed. A case study, based on data from an existing hydropower plant and referring to the Italian context in terms of operational constraints and ancillary service remuneration, is presented.
Keywords
battery storage system, frequency regulation, primary control reserve, renewables, run-of-river hydroelectric plant
Suggested Citation
Bignucolo F, Caldon R, Coppo M, Pasut F, Pettinà M. Integration of Lithium-Ion Battery Storage Systems in Hydroelectric Plants for Supplying Primary Control Reserve. (2019). LAPSE:2019.0760
Author Affiliations
Bignucolo F: Department of Industrial Engineering, University of Padova, 35131 Padova, Italy [ORCID]
Caldon R: Department of Industrial Engineering, University of Padova, 35131 Padova, Italy
Coppo M: Department of Industrial Engineering, University of Padova, 35131 Padova, Italy
Pasut F: S.T.E. Energy SpA, 35141 Padova, Italy
Pettinà M: Department of Industrial Engineering, University of Padova, 35131 Padova, Italy
[Login] to see author email addresses.
Journal Name
Energies
Volume
10
Issue
1
Article Number
E98
Year
2017
Publication Date
2017-01-14
Published Version
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en10010098, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2019.0760
This Record
External Link

doi:10.3390/en10010098
Publisher Version
Download
Files
[Download 1v1.pdf] (4.7 MB)
Jul 26, 2019
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
460
Version History
[v1] (Original Submission)
Jul 26, 2019
 
Verified by curator on
Jul 26, 2019
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2019.0760
 
Original Submitter
Calvin Tsay
Links to Related Works
Directly Related to This Work
Publisher Version