Abstract
In response to the poor reliability in identifying fault direction in distribution networks with Inverter Interfaced Distributed Generators (IIDGs), considering the control strategy of low-voltage ride-through, a fault direction criterion based on post-fault positive-sequence steady-state components is proposed. Firstly, the output steady-state characteristics of IIDGs considering the low-voltage ride-through capability are analyzed during grid failure, and the applicability of existing directional elements in a distribution network with IIDGs connected dispersively is demonstrated. Subsequently, for the typical structure of an active distribution grid operating under flexible modes, the positive-sequence voltage and current are examined in various fault scenarios, and a reliable direction criterion is suggested based on the difference in post-fault positive-sequence impedance angles on different sides of the lines that are suitable whether on the grid side or the IIDG side. Lastly, the reliability of the proposed direction criterion is verified by simulation and the results indicate that the fault direction can be correctly determined, whereas phase-to-phase and three-phase short circuit faults occur in different scenarios, independent of the penetration and grid-connected positions of IIDGs, fault location, and transition resistance. It is suitable for fault direction discrimination of an IIDGs multi-point grid-connected system under a flexible operation mode.
Keywords
direction criterion, flexible operation mode, IIDG, positive-sequence component, renewable energy system
Suggested Citation
Yang F, Chen H, Han G, Xu H, Lei Y, Hu W, Fan S. A Fault Direction Criterion Based on Post-Fault Positive-Sequence Information for Inverter Interfaced Distributed Generators Multi-Point Grid-Connected System. (2024). LAPSE:2024.1877
Author Affiliations
Yang F: State Grid Hubei Electric Power Co., Ltd., Wuhan 430077, China
Chen H: State Grid Hubei Electric Power Co., Ltd., Wuhan 430077, China
Han G: State Grid Hubei Electric Power Co., Ltd., Wuhan 430077, China
Xu H: College of Electrical Engineering and Automation, Shandong University of Science and Technology, Qingdao 266590, China
Lei Y: State Grid Hubei Electric Power Co., Ltd., Wuhan 430077, China
Hu W: State Grid Hubei Electric Power Co., Ltd., Wuhan 430077, China
Fan S: College of Electrical Engineering and Automation, Shandong University of Science and Technology, Qingdao 266590, China
Journal Name
Processes
Volume
12
Issue
7
First Page
1522
Year
2024
Publication Date
2024-07-19
ISSN
2227-9717
Version Comments
Original Submission
Other Meta
PII: pr12071522, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2024.1877
This Record
External Link

https://doi.org/10.3390/pr12071522
Publisher Version
Download
Files
Aug 23, 2024
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
431
Version History
[v1] (Original Submission)
Aug 23, 2024
 
Verified by curator on
Aug 23, 2024
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2024.1877
 
Record Owner
PSE Press
Links to Related Works
Directly Related to This Work
Publisher Version