Investigating the In-Flow Characteristics of Multi-Operation Conditions of Cross-Flow Fan in Air Conditioning Systems
Weijie Zhang, Jianping Yuan, Qiaorui Si, Yanxia Fu
January 19, 2020
Cross-flow fans are widely used in numerous applications such as low-pressure ventilation, household appliances, laser instruments, and air-conditioning equipment. Cross-flow fans have superior characteristics, including simple structure, small size, stable airflow, high dynamic pressure coefficient, and low noise. In the present study, numerical simulation and experimental research were carried out to study the unique secondary flow and eccentric vortex flow characteristics of the internal flow field in multi-operating conditions. To this end the vorticity and the circumferential pressure distribution in the air duct are obtained based on the performed experiments and the correlation between spectral characteristics of multiple operating conditions and the inflow state is established. The obtained results show that when the area of the airflow passage decreases while the area of the eccentric vortex area gradually increases, then the airflow of the cross-flow fan decreases, the outlet expands, and the flow pattern uniformity reduces. It was found that wakes form in the vicinity of the blade and the tail of the volute tongue, which generate pressure pulsation, and aerodynamic noise. The pressure distribution along the inner circumference shows that the total minimum pressure appears in the eccentric vortex near the volute tongue and the volute returns near the zone. Moreover, it was found that the total pressure near the eccentric vortex is significantly smaller than that of the main flow zone. As the flow rate decreases, the pressure pulsation amplitude of the eccentric vortex region significantly increases, while the static and total pressure pulsation amplitudes are gradually increased. Close to the eccentric vortex on the inner side of the blade in the volute tongue area, total pressure is low, total pressure on the outside of the blade is not affected, and pressure difference between the inner and outer sides is large. When the flow rate of the cross-flow fan is 0.4 Qd, there is no obvious peak at the harmonic frequency of the blade passage frequency. This shows that the aerodynamic noise is caused by the main unstable flow.
Keywords
cross-flow fan, internal flow, multi-operating condition, pressure fluctuation, the aerodynamic noise
Suggested Citation
Zhang W, Yuan J, Si Q, Fu Y. Investigating the In-Flow Characteristics of Multi-Operation Conditions of Cross-Flow Fan in Air Conditioning Systems. (2020). LAPSE:2020.0100
Author Affiliations
Zhang W: National Research Center of Pumps, Jiangsu University, Zhenjiang 212013, China
Yuan J: National Research Center of Pumps, Jiangsu University, Zhenjiang 212013, China
Si Q: National Research Center of Pumps, Jiangsu University, Zhenjiang 212013, China
Fu Y: School of Energy and Power Engineering, Jiangsu University, Zhenjiang 212013, China
Journal Name
Processes
Volume
7
Issue
12
Article Number
E959
Year
2019
Publication Date
2019-12-15
Published Version
ISSN
2227-9717
Version Comments
Original Submission
Other Meta
PII: pr7120959, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2020.0100
This Record
External Link

doi:10.3390/pr7120959
Publisher Version
Download
Files
Jan 19, 2020
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
605
Version History
[v1] (Original Submission)
Jan 19, 2020
 
Verified by curator on
Jan 19, 2020
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2020.0100
 
Original Submitter
Calvin Tsay
Links to Related Works
Directly Related to This Work
Publisher Version