Partial Discharge Measurement under an Oscillating Switching Impulse: A Potential Supplement to the Conventional Insulation Examination in the Field
Ming Ren, Ming Dong, Chongxing Zhang, Jierui Zhou
January 30, 2019
Partial discharge (PD) detection under oscillating switching impulse (OSI) voltage was performed on three types of insulation defects, including a protrusion on a conductor, a particle on an insulator surface, and a void in an insulator, which are three kinds of the common potential insulation hazards in gas insulated power apparatus. Experiment indicated that the PD sequences under OSI were composed of various combinations of the single pulse, the multiple pulses, and the reverse polarity pulse. The difference between the PD inception voltage (PDIV) and the breakdown voltage (BDV) under OSI voltage was greater than that under alternating current (AC) voltage in some cases, which can provide a more sufficient margin below the BDV for PD diagnosis. The OSI voltage also showed a better performance for exciting PDs with detectable magnitudes from small-scale defects, of which the AC voltage was incapable under our test conditions. The different PD activities with different interfaces under an impulse and a slowly varying voltage were speculated to be associated with the gradient of the background electric field and the space-charge mobility.
Keywords
gas insulated switchgear, impulse voltage, insulation diagnosis, partial discharge, power apparatus, SF6
Suggested Citation
Ren M, Dong M, Zhang C, Zhou J. Partial Discharge Measurement under an Oscillating Switching Impulse: A Potential Supplement to the Conventional Insulation Examination in the Field. (2019). LAPSE:2019.0135
Author Affiliations
Ren M: State Key Laboratory of Electrical Insulation for Power Equipment, Xi’an Jiaotong University, Xi’an 710049, China
Dong M: State Key Laboratory of Electrical Insulation for Power Equipment, Xi’an Jiaotong University, Xi’an 710049, China
Zhang C: State Key Laboratory of Electrical Insulation for Power Equipment, Xi’an Jiaotong University, Xi’an 710049, China [ORCID]
Zhou J: State Key Laboratory of Electrical Insulation for Power Equipment, Xi’an Jiaotong University, Xi’an 710049, China [ORCID]
[Login] to see author email addresses.
Journal Name
Energies
Volume
9
Issue
8
Article Number
E623
Year
2016
Publication Date
2016-08-09
Published Version
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en9080623, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2019.0135
This Record
External Link

doi:10.3390/en9080623
Publisher Version
Download
Files
[Download 1v1.pdf] (6.5 MB)
Jan 30, 2019
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
558
Version History
[v1] (Original Submission)
Jan 30, 2019
 
Verified by curator on
Jan 30, 2019
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2019.0135
 
Original Submitter
Calvin Tsay
Links to Related Works
Directly Related to This Work
Publisher Version