The Applicability of Traditional Protection Methods to Lines Emanating from VSC-HVDC Interconnectors and a Novel Protection Principle
Shimin Xue, Jingyue Yang, Yanxia Chen, Cunping Wang, Zhe Shi, Miao Cui, Botong Li
November 28, 2018
Voltage source converter (VSC)-based high voltage direct current (VSC-HVDC) interconnectors can realize accurate and fast control of power transmission among AC networks, and provide emergency power support for AC networks. VSC-HVDC interconnectors bring exclusive fault characteristics to AC networks, thus influencing the performance of traditional protections. Since fault characteristics are related to the control schemes of interconnectors, a fault ride-through (FRT) strategy which is applicable to the interconnector operating characteristic of working in four quadrants and capable of eliminating negative-sequence currents under unbalanced fault conditions is proposed first. Then, the additional terms of measured impedances of distance relays caused by fault resistances are derived using a symmetrical component method. Theoretical analysis shows the output currents of interconnectors are controllable after faults, which may cause malfunctions in distance protections installed on lines emanating from interconnectors under the effect of fault resistances. Pilot protection is also inapplicable to lines emanating from interconnectors. Furthermore, a novel pilot protection principle based on the ratio between phase currents and the ratio between negative-sequence currents flowing through both sides is proposed for lines emanating from the interconnectors whose control scheme aims at eliminating negative-sequence currents. The validity of theoretical analysis and the protection principle is verified by PSCAD/EMTDC simulations.
Keywords
distance protection, fault resistance, fault ride through (FRT), pilot protection, VSC-HVDC interconnector
Suggested Citation
Xue S, Yang J, Chen Y, Wang C, Shi Z, Cui M, Li B. The Applicability of Traditional Protection Methods to Lines Emanating from VSC-HVDC Interconnectors and a Novel Protection Principle. (2018). LAPSE:2018.1099
Author Affiliations
Xue S: Key Laboratory of Smart Grid of Ministry of Education, Tianjin University, Tianjin 300072, China
Yang J: Key Laboratory of Smart Grid of Ministry of Education, Tianjin University, Tianjin 300072, China
Chen Y: Beijing Electric Power Corporation, Beijing 100075, China
Wang C: Beijing Electric Power Corporation, Beijing 100075, China
Shi Z: Key Laboratory of Smart Grid of Ministry of Education, Tianjin University, Tianjin 300072, China
Cui M: Key Laboratory of Smart Grid of Ministry of Education, Tianjin University, Tianjin 300072, China
Li B: Key Laboratory of Smart Grid of Ministry of Education, Tianjin University, Tianjin 300072, China [ORCID]
[Login] to see author email addresses.
Journal Name
Energies
Volume
9
Issue
6
Article Number
E400
Year
2016
Publication Date
2016-05-25
Published Version
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en9060400, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2018.1099
This Record
External Link

doi:10.3390/en9060400
Publisher Version
Download
Files
[Download 1v1.pdf] (10.1 MB)
Nov 28, 2018
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
627
Version History
[v1] (Original Submission)
Nov 28, 2018
 
Verified by curator on
Nov 28, 2018
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2018.1099
 
Original Submitter
Calvin Tsay
Links to Related Works
Directly Related to This Work
Publisher Version