Abstract
This paper presents an improved current control strategy for a three-phase grid-connected inverter under distorted grid conditions. The main challenge associated with the grid-connected inverter in distributed generation (DG) systems is to maintain the harmonic contents in output current below the specified values even when the grid is subject to uncertain disturbances such as harmonic distortion. To overcome such a challenge, an improved current control scheme is proposed for a grid-connected inverter, in which the fundamental and harmonic currents are independently controlled by a proportional-integral (PI) decoupling controller and a predictive basis controller, respectively. The controller design approach is based on the model decomposition method, where the measured inverter currents and grid voltages are divided into the fundamental and harmonic components by means of moving average filters (MAFs). Moreover, to detect the angular displacement and angular frequency with better accuracy, even in the presence of the grid disturbance, the MAF is also introduced to implement an enhanced phase-lock loop (PLL) structure. Theoretical analyses as well as comparative simulation results demonstrate that the proposed control scheme can effectively compensate the uncertainties caused by the grid voltages with fast transient response. To validate the feasibility of the proposed scheme, the whole control algorithms are implemented on 2 kVA three-phase grid-connected inverter system using 32-bit floating-point DSP TMS320F28335. As a result, the proposed scheme is an attractive way to control a grid-connected inverter under adverse grid conditions.
Keywords
current control, distorted grid conditions, DSP TMS320F28335, grid-connected inverter, model decomposition, moving average filter
Suggested Citation
Lai NB, Kim KH. An Improved Current Control Strategy for a Grid-Connected Inverter under Distorted Grid Conditions. (2018). LAPSE:2018.0923
Author Affiliations
Lai NB: Department of Electrical and Information Engineering, Seoul National University of Science and Technology, 232 Gongneung-ro, Nowon-gu, Seoul 139-743, Korea [ORCID]
Kim KH: Department of Electrical and Information Engineering, Seoul National University of Science and Technology, 232 Gongneung-ro, Nowon-gu, Seoul 139-743, Korea [ORCID]
[Login] to see author email addresses.
Journal Name
Energies
Volume
9
Issue
3
Article Number
E190
Year
2016
Publication Date
2016-03-12
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en9030190, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2018.0923
This Record
External Link

https://doi.org/10.3390/en9030190
Publisher Version
Download
Files
Nov 27, 2018
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
1239
Version History
[v1] (Original Submission)
Nov 27, 2018
 
Verified by curator on
Nov 27, 2018
This Version Number
v1
Citations
Most Recent
This Version
URL Here
http://psecommunity.org/LAPSE:2018.0923
 
Record Owner
Calvin Tsay
Links to Related Works
Directly Related to This Work
Publisher Version
(0.07 seconds)

[0.07 s]