LAPSE:2018.0480
Published Article
LAPSE:2018.0480
Dual-Temperature Evaluation of a High-Temperature Insulation System for Liquid-Immersed Transformer
Xiaojing Zhang, Lu Ren, Haichuan Yu, Yang Xu, Qingquan Lei, Xin Li, Baojia Han
September 21, 2018
A high-temperature oil⁻paper insulation system offers an opportunity to improve the overloading capability of distribution transformers facing seasonal load variation. A high-temperature electrical insulation system (EIS) was chosen due to thermal calculation based on a typical loading curve on the China Southern Power Grid. In order to evaluate candidate high-temperature insulation systems, Nomex® T910 (aramid-enhanced cellulose) immersed in FR3 (natural ester) was investigated by a dual-temperature thermal aging test compared with a conventional insulation system, Kraft paper impregnated with mineral oil. Throughout the thermal aging test, mechanical, chemical, and dielectric parameters of both paper and insulating oil were investigated in each aging cycle. The thermal aging results determined that the thermal class of the FR3-T910 insulation system meets the request of overloading transformer needs.
Keywords
dual-temperature, liquid-immersed transformer, natural ester, Nomex T910, thermal aging
Subject
Suggested Citation
Zhang X, Ren L, Yu H, Xu Y, Lei Q, Li X, Han B. Dual-Temperature Evaluation of a High-Temperature Insulation System for Liquid-Immersed Transformer. (2018). LAPSE:2018.0480
Author Affiliations
Zhang X: State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, No.28 Xianning West Road, Xi’an 710049, China
Ren L: State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, No.28 Xianning West Road, Xi’an 710049, China
Yu H: State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, No.28 Xianning West Road, Xi’an 710049, China
Xu Y: State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, No.28 Xianning West Road, Xi’an 710049, China
Lei Q: State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, No.28 Xianning West Road, Xi’an 710049, China
Li X: Electric Power Research Institute of Guangdong Power Grid Corporation, No.6–8 Dongfeng East Road, Guangzhou 510062, China
Han B: Guangdong Zhongpeng Electricity Co., Ltd., No.19 Qianjin Road, Foshan 528000, China
[Login] to see author email addresses.
Journal Name
Energies
Volume
11
Issue
8
Article Number
E1957
Year
2018
Publication Date
2018-07-27
Published Version
ISSN
1996-1073
Version Comments
Original Submission
Other Meta
PII: en11081957, Publication Type: Journal Article
Record Map
Published Article

LAPSE:2018.0480
This Record
External Link

doi:10.3390/en11081957
Publisher Version
Download
Files
[Download 1v1.pdf] (4.7 MB)
Sep 21, 2018
Main Article
License
CC BY 4.0
Meta
Record Statistics
Record Views
476
Version History
[v1] (Original Submission)
Sep 21, 2018
 
Verified by curator on
Sep 21, 2018
This Version Number
v1
Citations
Most Recent
This Version
URL Here
https://psecommunity.org/LAPSE:2018.0480
 
Original Submitter
Calvin Tsay
Links to Related Works
Directly Related to This Work
Publisher Version